Variable Mode Operation
Variable mode operation is when signal operation changes between
protected-only to protected-permissive mode, or between protected-permissive
to permissive-only operation based on the time of day. It is possible
with the 4-section FYA signal face when a study shows this type
of operation to be beneficial. However, you must ensure that the
controller is capable of switching between modes such that the flashing
yellow arrow indication and the opposing through movement indication
terminate together.
In other words, the controller should be capable of transitioning
between modes without the flashing yellow arrow terminating while
the opposing through movement stays green. Additionally, when switching
between protected-permissive to permissive-only mode, ensure that
the controller is capable of reassigning the left-turn detectors
to call the associated through phases by time of day.