Section 6: Non-Contact Lap Splices
General
Where a traditional lap splice is not possible, such as where columns are stepped or drilled shafts frame into to dissimilarly shaped or sized columns, use a non-contact lap splice. Depending on the geometry of the two connected elements, non-contact lap splices will need to be provided in either the lower element, the upper element, or both elements.
Detailing
When calculating the required lap length,
, use reinforcement confinement factor,
λrc, of 1.0.
, use reinforcement confinement factor,
λrc, of 1.0.
Provide a total splice length:
, where
equals the maximum lateral spacing between longitudinal reinforcement transferring the force.
, where
equals the maximum lateral spacing between longitudinal reinforcement transferring the force.
Provide transverse reinforcement along the provided splice length that satisfies the following requirements:
- For laps confined by spiral reinforcing, provide transverse reinforcement that satisfies Equation 5.10.8.4.2a-1.
- For laps confined by stirrups, provide transverse reinforcement spaced no wider than the maximum allowed spacing of transverse reinforcement, smax
, for each face of the column. Observe minimum spacing requirements for concrete consolidation as outlined inAASHTO LRFD Bridge Design Specifications. Use the following equation to determine the maximum allowed spacing of transverse reinforcement for each face:
=
where:
= number of legs of column transverse reinforcement, perpendicular to face of the column
= area of column transverse reinforcement (in2 )
= specified minimum yield strength of column transverse reinforcement (ksi)
= standard required splice length (in)
= Total area of longitudinal reinforcement in tension at face of the column (in2 )
= = ultimate strength of longitudinal reinforcement (ksi)