Branch Circuit Amps
The branch circuit amps column contains the actual
expected load in amps for each branch circuit. For non-lighting
circuits, the breaker size is typically the smallest standard size
larger than the computed load. For lighting circuits, the breaker
size is typically the smallest standard size larger than 125% of