Conduit Run Length

As conduit run length and number of bends increases, the effort required to pull conductors also increases. Generally continuous conduit runs in excess of 700 feet are not recommended. Continuous conduit runs in excess 500 feet are not recommended when bends total 180 degrees. The NEC limits total conduit bends between pulling points to 360 degrees (no matter what the length of the run).