Conductor Resistance
To calculate voltage drop, you need to know the resistance
of the conductor (wire) used in the branch circuit. Resistance is
a function of wire size and length. Resistance for both wires going
to the luminaire must be considered.
The following table shows wire resistance for various American
Wire Gauges (AWG). Since both wires are the same size in typical
circuits, the table shows “loop resistance”; thus the designer need only
calculate the distance between luminaire poles.
Wire Size | Loop Wire Resistance* | |
---|---|---|
(AWG) | (ohms/foot) | (ohms/meter) |
12 | 0.003360 | 0.011023 |
10 | 0.002036 | 0.006680 |
8 | 0.001308 | 0.004291 |
6 | 0.000820 | 0.002690 |
4 | 0.000518 | 0.001700 |
2 | 0.000324 | 0.001063 |
0 | 0.000204 | 0.000670 |
00 | 0.000162 | 0.000532 |
* Values shown
are for uncoated copper conductors in conduit at 25°C |
Loop resistance accounts for the wire run in both directions,
requiring the designer to measure only the one-way distance between
luminaire poles.
Larger wire sizes have lower resistances. Using larger wire
is one way to reduce the voltage drop in the circuit.