Legacy Procedure of Driven Piles from TCP
When using TCP information for driven piles, designs generally rely solely on skin friction capacity and partial to no capacity is generated by end bearing.
Application of the (0.7) reduction factor to the design of driven piling is not necessary
as these are displacement piles and do not remove subsurface soils as with drilled shafts.Calculate total allowable skin friction by multiplying the perimeter of the pile by the unit value for allowable skin friction derived from Figure A1-2, Figure A1-4, or laboratory data or a combination thereof. The maximum recommended value for allowable skin friction for piling is 1.4 tons per square foot (TSF). Accumulate skin friction along the length of the pile beginning at the previously defined disregard depth and continuing down to the tip of the pile. If using point bearing, calculate total allowable point bearing by multiplying the area of the pile times the unit value for allowable point bearing derived from Figure A1-3, Figure A1-5, or laboratory data. If softer layers exist within two diameters of the proposed tip, use allowable point bearing values based on the softer layers.
Displacement piling typically refuses to advance once material with TCP values harder than 100 blows/12 in are encountered.
-Evaluation-/Legacy-Procedure-of-Driven-Piles-from-TCP/Allowable_Skin_Friction.png/_jcr_content/renditions/original)
Figure A1-2. Allowable Skin Friction (TCP Values Softer than 100 Blows/12 in.)
Use Figure A1-2 to determine allowable skin friction capacity for soil softer than 100 blows/12 in. Select the curve based on the description of the soil type.
Use Figure A1-3 to determine allowable point bearing for soil softer than 100 blows/12 in. Select the curve based on the description of the soil type, using the criteria noted for the previous chart.
-Evaluation-/Legacy-Procedure-of-Driven-Piles-from-TCP/Allowable_Point_Bearing.png/_jcr_content/renditions/original)
Figure A1-3. Allowable Point Bearing (TCP Values Softer than 100 Blows/12 in.)
Use Figure A1-4 to determine allowable skin friction for soil or rock strata harder than 100 blows/12 in. The upper limit of 3.25 tons/ft2 applies for all Texas Cone Penetration values less than 2 in/100 blows. Do not apply skin friction reduction factor to values obtained from this figure because this figure is derived only for use in drilled shaft design. Piling typically cannot be driven into soil of this strength, so this figure is not generally used for piling.
-Evaluation-/Legacy-Procedure-of-Driven-Piles-from-TCP/Allowable_Skin_Friction_TCP_Values_Harder_than_100_Blows_12_in.png/_jcr_content/renditions/original)
Figure A1-4. Allowable Skin Friction (TCP Values Harder than 100 Blows/12 in.)
Use Figure A1-5 to determine allowable point bearing for soil or rock strata harder than 100 blows/12 in. The upper limit of 31 tons/ft2 applies for all Texas Cone Penetration values less than 2 in/100 blows.
-Evaluation-/Legacy-Procedure-of-Driven-Piles-from-TCP/Allowable_Point_Bearing_TCP_Values_Harder_than_100_Blows_12_in.png/_jcr_content/renditions/original)
Figure A1-5. Allowable Point Bearing (TCP Values Harder than 100 Blows/12 in.)