Overview

Piling design should consider skin friction and may consider point bearing as well. Because piling has small tip areas and is generally placed in softer soil, the point bearing contribution is modest and is often disregarded in design.
Calculate total allowable skin friction by multiplying the perimeter of the pile by the unit value for allowable skin friction derived from Figure 5-1, Figure 5-3, or laboratory data or a combination thereof. The maximum recommended value for allowable skin friction for piling design is 1.4 tons per square foot (TSF). Accumulate skin friction along the length of the pile beginning at the previously defined disregard depth and continuing down to the tip of the pile. If using point bearing, calculate total allowable point bearing by multiplying the area of the pile times the unit value for allowable point bearing derived from Figure 5-2, Figure 5-4, or laboratory data. If softer layers exist within two shaft diameters of the proposed tip, use allowable point bearing values based on the softer layers. Displacement piling refuses to advance when it encounters material with TCP values harder than 100 blows/12 in. On refusal, assume that the piling has developed the maximum allowable service load for the pile.
Take care when designing piling in areas with shallow hard or dense soils. If piling cannot be driven through these areas, the contractor will need to pilot hole or jet the piling to achieve the desired penetration.